{"id":2757,"date":"2026-11-26T08:18:53","date_gmt":"2026-11-26T11:18:53","guid":{"rendered":"https:\/\/thermomac.com\/?p=2757"},"modified":"2026-11-26T08:18:57","modified_gmt":"2026-11-26T11:18:57","slug":"tecnologias-de-deteccion-de-gases-cual-elegir-en-una-planta-de-refrigeracion-industrial","status":"publish","type":"post","link":"https:\/\/thermomac.com\/en\/tecnologias-de-deteccion-de-gases-cual-elegir-en-una-planta-de-refrigeracion-industrial\/","title":{"rendered":"Gas detection technologies: which one to choose for an industrial refrigeration plant"},"content":{"rendered":"<p class=\"wp-block-paragraph\"><strong>Gas detection in refrigeration, part 2.<\/strong><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">In the <a href=\"https:\/\/thermomac.com\/esperar-a-que-la-fuga-se-vea-sale-caro\/\">first part<\/a> we looked at how much it costs to wait until a leak becomes visible and what sequence ANSI\/IIAR 2-2021 requires at 25, 150 and 40,000 ppm. Now the practical question: which technology detects what? None of them works for every application. That is why manufacturers such as MSA Safety recommend combining several of them in layers of protection. This is an overview of the main technologies and their place in industrial refrigeration.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Electrochemical (EC)<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">The sensor works as a transducer: an electrolyte and a pair of electrodes generate a current proportional to the gas concentration. There are specific cells for each toxic gas.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Where it fits: toxic gases in the ppm range and oxygen monitoring in confined spaces. In refrigeration it is the usual technology for detecting ammonia leaks at low levels, the zone of the 25 ppm alarm. For ammonia, ranges of 0 to 100 ppm and 0 to 1,000 ppm are used, and the compact format makes it practical in rooms with many valves and flanges.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">What you need to know: it can be cross-sensitive to other gases, which, depending on the case, make it read high or low. And in a conventional cell the electrolyte is consumed as it reacts with ammonia: rated life is 1 to 2 years, but with high concentrations or extreme temperature and humidity it can drop to months or weeks, and it is hard to predict when it starts losing sensitivity. That is why it requires frequent calibration.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">MSA's XCell sensors solve much of this with two design changes: an ionic liquid electrolyte that does not evaporate and a catalyst that is not consumed by the gas. They withstand -40 \u00b0C to +60 \u00b0C, contact with ammonia barely shortens their life, they last more than 5 years and come with a 3-year warranty. In a low-temperature cold room or a very humid machine room, that range matters.<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/thermomac.com\/wp-content\/uploads\/2026\/11\/d02-xcell-es.png\" alt=\"Estructura de una celda electroqu\u00edmica XCell. Imagen: MSA Safety\"\/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\"><\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Catalytic bead (CB)<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">A catalyst-coated filament is heated and burns the combustible gas that reaches its surface. The extra heat changes its electrical resistance, and a Wheatstone bridge, with a second reference element that compensates for temperature, pressure and humidity, converts that change into a signal.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Where it fits: combustible gases in %LEL (hydrocarbons, hydrogen), with a range of 0 to 100 %LEL. It performs well in extreme temperatures, humidity and vibration. In NH3 plants it is used in compressor rooms with a large inventory, where a major leak could approach the flammable range. Its limitation: it responds to any combustible gas, so it does not always tell you which one it is.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Point infrared (PIR)<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">It measures how much of an infrared beam the gas absorbs, compared with a reference beam that the gas does not absorb.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Where it fits: hard-to-reach locations, such as ducts or ceiling spaces, because it requires little maintenance. Being optical, it is not poisoned by silicones or halogenated compounds. In refrigeration it is the reference option for CO2 (R744) and for many HFC and HFO refrigerants. Note: it does not detect hydrogen.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Multipoint photoacoustic infrared (PAIR)<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">It is a variant of infrared designed for ammonia. A central analyzer draws air, in turn, from up to 16 sampling points and measures ammonia by infrared absorption, which it converts into an acoustic signal. Range: 0 to 1,000 ppm.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Where it fits: machine rooms, pump rooms and cold storage rooms with many points to monitor (joints, flanges, valves). MSA specifically recommends it for warehouses and cold storage facilities, with its Chillgard 5000 monitor. It is highly specific to ammonia, unaffected by other gases or corrosive environments, remains stable even with frequent gas exposure, and the sensor lasts more than 5 years. It also has an advantage built into its principle: if there is no gas, there is no pressure pulse, so zero is a true zero. Neither changes in temperature or pressure nor aging of the lamp or microphone cause it to drift. The drawback: the sample takes time to reach the analyzer when the point is far away, at the maximum allowed tubing length. It is the same sampling principle we saw in the first part for halogenated refrigerants, applied to ammonia.<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/thermomac.com\/wp-content\/uploads\/2026\/11\/d02-pair-es.png\" alt=\"Esquema de un detector fotoac\u00fastico. Imagen: MSA Safety\"\/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\"><\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Catalytic or infrared: the most frequently asked comparison<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">MSA devoted a full article to this comparison, and its conclusion holds for our plants: neither is better overall; it depends on the gas, the environment and the maintenance the plant can sustain. The differences worth being clear about:<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">1) <strong>Poisoning.<\/strong> A catalytic sensor can lose sensitivity due to silicones or hydrogen sulfide. In a cold storage plant this is not theoretical: silicone sealants are common in panels and cold rooms. Infrared, being optical, does not get poisoned.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">2) <strong>Oxygen.<\/strong> A catalytic sensor needs oxygen to measure, because it measures combustion. Infrared does not, and keeps measuring in oxygen-deficient atmospheres.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">3) <strong>Prolonged exposure.<\/strong> Extended exposure to high concentrations, at or above the lower explosive limit, can affect a catalytic sensor over time. Infrared is designed to operate with the continuous presence of gas.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">4) <strong>Hydrogen.<\/strong> Catalytic sensors detect it; conventional infrared does not, because hydrogen does not absorb infrared.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">5) <strong>Maintenance.<\/strong> Catalytic sensors require periodic bump tests and calibration checks. Infrared can extend calibration intervals according to site procedures, but its optical surfaces need cleaning in dusty, humid or corrosive environments.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">6) <strong>Cost.<\/strong> Catalytic is usually cheaper upfront; infrared costs more upfront and requires less sensor maintenance.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">In refrigeration, this translates as follows: for CO2 and halogenated refrigerants, infrared; for hydrocarbon refrigerants (R290, R600a, R1270), infrared or catalytic depending on the environment; and for ammonia, electrochemical or multipoint photoacoustic in the low ppm range and a high-range technology for concentrations close to the flammable range. Many plants end up using both technologies at once, each where it performs best.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Open-path infrared (OPIR)<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">It uses the same principle, but with a beam of more than 100 meters between transmitter and receiver (or reflector), and detects the gas cloud crossing it.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Where it fits: large open areas or a line of potential leak sources, such as a row of tanks, valves or pumps.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Laser (ELDS)<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">It analyzes the specific spectral \"fingerprint\" of each gas, which reduces false alarms from interfering gases almost to zero. It is not poisoned either.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Where it fits: perimeter monitoring, to detect a toxic gas leaving the plant boundaries. It works with path lengths of 5 to 40 meters or 40 to 120 meters, is unaffected by rain, fog or snow, and requires no calibration. It is not suitable for highly congested equipment areas, and it does not give the concentration at a single point.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Ultrasonic (UGLD)<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">It does not measure concentration: it \"listens\" for the ultrasonic noise of a pressurized gas leak and estimates its leak rate. The gas does not need to reach the sensor.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Where it fits: outdoor installations and highly ventilated environments, where gas disperses before reaching a point detector. It covers 17 to 28 meters depending on the microphone, but only works in installations pressurized at 2 bar or more. In refrigeration, that leaves out much of the low side: in low-temperature systems, suction usually operates below that pressure.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">One sensor does not cover the whole sequence<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Back to the standard. The ANSI\/IIAR 2-2021 sequence runs from 25 ppm (alarm) to 40,000 ppm (shutdown of compressors and pumps), and 40,000 ppm is 25 % of the lower flammable limit of ammonia. That is more than three orders of magnitude. A sensor optimized to read accurately around 25 ppm is not the same one that reliably measures tens of thousands of ppm. That is why, in a well-designed machine room, the technology is chosen based on which threshold each detector must trigger, and not only on \"which gas is present\".<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Layered protection<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">The first line of defense is point detectors, located next to likely leak sources: compressors, valves, pumps, vessels and piping. Adding ultrasonic or laser detection adds layers that protect people, equipment and the facility.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">To choose well, you need to consider:<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">1) The gas: NH3, CO2, HFC\/HFO or hydrocarbons.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">2) The range to measure: ppm for personnel exposure, %LEL for explosion risk.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">3) The environment: temperature, humidity, ventilation, vibration, indoor or outdoor, and the presence of silicones or other sensor contaminants.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">4) The maintenance and calibration the plant can sustain over time, which, as we saw with IIAR 6-2025, must be documented.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">How can we help you?<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">At Thermomac we are distributors of the MSA Bacharach gas detection line, and we advise on sensor selection, detector placement and integration with the plant control system. If you are about to expand or upgrade the gas detection in your machine room, write to us at info@thermomac.com.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><em>Sources: MSA Safety, \"Solutions for Ammonia Gas Detection: A Comparison Summary\" (white paper, 2026), \"Sensor Technologies for Ammonia Detection\" (technical guide) and \"Ammonia Detection Solutions\"; MSA Safety, \"A Review of the Gas Detection Technologies Available to You\" (2026) and \"Infrared vs Catalytic Bead Gas Detectors: Key Differences Explained\" (10\/8\/2026), Spotlight on Safety blog; ANSI\/IIAR 2-2021, International Institute of Ammonia Refrigeration. Thermomac is a corporate member of IIAR and a channel partner for the MSA Bacharach detection line.<\/em><\/p>","protected":false},"excerpt":{"rendered":"<p>Detecci\u00f3n de gases en refrigeraci\u00f3n, entrega 2. En la primera entrega vimos cu\u00e1nto cuesta esperar a que una fuga se vea y qu\u00e9 secuencia exige la ANSI\/IIAR 2-2021 a 25, 150 y 40.000 ppm. Ahora la pregunta pr\u00e1ctica: \u00bfcon qu\u00e9 tecnolog\u00eda se detecta cada cosa? Ninguna sirve para todas las aplicaciones. Por eso los fabricantes, [&hellip;]<\/p>\n","protected":false},"author":2,"featured_media":2760,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"site-sidebar-layout":"default","site-content-layout":"","ast-site-content-layout":"default","site-content-style":"default","site-sidebar-style":"default","ast-global-header-display":"","ast-banner-title-visibility":"","ast-main-header-display":"","ast-hfb-above-header-display":"","ast-hfb-below-header-display":"","ast-hfb-mobile-header-display":"","site-post-title":"","ast-breadcrumbs-content":"","ast-featured-img":"","footer-sml-layout":"","ast-disable-related-posts":"","theme-transparent-header-meta":"","adv-header-id-meta":"","stick-header-meta":"","header-above-stick-meta":"","header-main-stick-meta":"","header-below-stick-meta":"","astra-migrate-meta-layouts":"set","ast-page-background-enabled":"default","ast-page-background-meta":{"desktop":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ast-content-background-meta":{"desktop":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"_joinchat":[],"footnotes":""},"categories":[17],"tags":[],"class_list":["post-2757","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-deteccion-de-gases"],"_links":{"self":[{"href":"https:\/\/thermomac.com\/en\/wp-json\/wp\/v2\/posts\/2757","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/thermomac.com\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/thermomac.com\/en\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/thermomac.com\/en\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/thermomac.com\/en\/wp-json\/wp\/v2\/comments?post=2757"}],"version-history":[{"count":1,"href":"https:\/\/thermomac.com\/en\/wp-json\/wp\/v2\/posts\/2757\/revisions"}],"predecessor-version":[{"id":2761,"href":"https:\/\/thermomac.com\/en\/wp-json\/wp\/v2\/posts\/2757\/revisions\/2761"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/thermomac.com\/en\/wp-json\/wp\/v2\/media\/2760"}],"wp:attachment":[{"href":"https:\/\/thermomac.com\/en\/wp-json\/wp\/v2\/media?parent=2757"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/thermomac.com\/en\/wp-json\/wp\/v2\/categories?post=2757"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/thermomac.com\/en\/wp-json\/wp\/v2\/tags?post=2757"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}